Kanlux KSD-T2 275/40 M Surge Protection Module T2 | 23131
Artikelnummer:
23131
EAN:
5905339231314
NOVOOM SERVICE
Schneller Versand
Kauf auf Rechnung
Einfache Rückgabe
The Kanlux KSD-T2 275/40 M is a replaceable T2 class surge protection module for low-voltage distribution systems. It is designed for 230 V AC and offers defined protection values with a nominal discharge current of 20 kA and a maximum discharge current of 40 kA.
Advantages at a glance
- Surge protection type 2 / class C
- 1-pole module design
- Nominal discharge current 20 kA
- Maximum discharge current 40 kA
- Protection level ≤ 1.3 kV
- Wide temperature range from −40 to +70 °C
Technical data
| Type | T2 / class C |
| Number of poles | 1-pole |
| Modules | 1 |
| Nominal voltage | 230 V AC |
| Frequency | 50 Hz |
| Uc | 275 V |
| In | 20 kA |
| Imax | 40 kA |
| Up | ≤ 1.3 kV |
| Ipe | 30 µA |
| Itrans | 40 kA |
| Prospective short-circuit current | 100 A RMS |
| Protection rating | IP20 |
| Temperature range | −40 to +70 °C |
| Humidity | 5–95 % |
| Connection | Terminal block |
| Standard | PN-EN 61643-1 |
| Weight | 44 g |
Note: Installation and work on electrical distribution systems must only be carried out by appropriately qualified specialists.
Hinweis: Produktnamen sind Modellbezeichnungen; Hersteller oder Marke gelten nur als zugesichert, wenn diese ausdrücklich genannt werden.
Mehr Infos